Join 60,000+ competitive exam aspirants
Three phase overhead transmission line has its conductors horizontally spaced with spacing between adjacent conductors equals to d.┬а If now the conductors of the line are rearranged to form an equilateral triangle of sides equal to d. Then
Average capacitance and inductance will increase
Average capacitance will decrease and inductance will increase
Average capacitance will increase and inductance will decrease
Surge impedance loading of the line increases
Average capacitance will increase and inductance will decrease
In a horizontal transmission line, the Geometric Mean Distance (GMD) is 3dтЛЕdтЛЕ2dтАЛ=32тАЛdтЙИ1.26d. By rearranging the conductors into an equilateral triangle, the GMD reduces to d. Since inductance is proportional to ln(GMRGMDтАЛ) and capacitance is inversely proportional to ln(rGMDтАЛ), reducing the GMD decreases inductance and increases capacitance.
In a horizontal transmission line, the Geometric Mean Distance (GMD) is 3dтЛЕdтЛЕ2dтАЛ=32тАЛdтЙИ1.26d. By rearranging the conductors into an equilateral triangle, the GMD reduces to d. Since inductance is proportional to ln(GMRGMDтАЛ) and capacitance is inversely proportional to ln(rGMDтАЛ), reducing the GMD decreases inductance and increases capacitance.
L=2├Ч10тИТ7ln(GMRGMDтАЛ)┬аH/m тАФ Inductance per unit length
C=ln(rGMDтАЛ)2╧А╧╡0тАЛтАЛ┬аF/m тАФ Capacitance per unit length
The transmission line parameters depend on the mutual geometric relationship between conductors. When conductors are moved from a horizontal configuration to an equilateral configuration, the effective spacing (GMD) decreases. As L=2├Ч10тИТ7ln(GMRGMDтАЛ) and C=ln(rGMDтАЛ)2╧А╧╡тАЛ, a lower GMD leads to a direct reduction in the logarithmic term for inductance and an increase in the same for capacitance (due to the denominator in the capacitance formula).
Equilateral spacing results in balanced line parameters for all three phases.
Geometric Mean Distance (GMD) is the key geometric factor influencing line inductance and capacitance.
Transposition is not required for equilateral configurations to maintain balanced parameters.
Decreasing GMD improves line efficiency regarding inductive voltage drop.
Balanced voltage drops across all three phases.
Reduction in net series inductive reactance.
Mechanical complexity in tower design for equilateral configurations.
Higher line capacitance increases the charging current.
High Voltage (HV) transmission lines.
Power systems requiring balanced phase parameters.
| Feature | Horizontal | Equilateral |
|---|---|---|
GMD (Spacing) | 1.26d (Horizontal) | d (Equilateral) |
For the horizontal spacing case, GMD is 3d├Чd├Ч2dтАЛ=1.26d.
Option D is incorrect because Surge Impedance Loading (SIL) is defined as ZcтАЛV2тАЛтАЛ, where ZcтАЛ=CLтАЛтАЛ. Since L decreases and C increases, ZcтАЛ decreases, which actually increases the SIL capacity of the line.
C is correct тАФ rearranging to equilateral triangle reduces the Geometric Mean Distance (GMD), which decreases line inductance and increases line capacitance.
Always remember: Inductance and Capacitance are inverse in their sensitivity to GMD changes due to the logarithmic nature of the GMD term in their respective formulas.