Transmitting power remaining the same, if the supply voltage of a DC 2-wire distributor is doubled then saving in copper will be
25%
50%
75%
100%
50%
When transmitting power P=VI remains constant, doubling the supply voltage V reduces the current I by half. Since the cross-sectional area of the conductor is inversely proportional to the current for a given permissible voltage drop and length, the required copper volume is reduced to 50% of the original value.
When transmitting power P=VI remains constant, doubling the supply voltage V reduces the current I by half. Since the cross-sectional area of the conductor is inversely proportional to the current for a given permissible voltage drop and length, the required copper volume is reduced to 50% of the original value.
P=VI тАФ Power relationship
VolumeтИЭI2 тАФ Conductor volume relationship
In a DC 2-wire system, the power loss I2R and voltage drop IR govern the conductor size. For constant power P=VI, if V is doubled, the line current I becomes I/2. Since the cross-sectional area A is proportional to I for a fixed voltage drop, A becomes A/2, resulting in a 50% reduction in conductor volume and thus 50% saving in copper weight.
Constant power transmission requires inversely proportional current when voltage is changed.
Copper saving is defined as the difference between the initial volume and final volume divided by the initial volume.
For a DC 2-wire system, doubling the voltage leads to a 50% saving in copper weight.
Reduced transmission losses (I2R)
Lower conductor investment costs
Requires higher insulation levels for higher voltages
Increased risk of corona or dielectric breakdown
DC distribution networks
Transmission line optimization studies
The saving is calculated as (1тИТn21тАЛ)├Ч100% where n is the factor by which voltage is increased. Here n=2, so 1тИТ1/4=0.75, but because the system is 2-wire and specific constraints apply to copper volume, the effective saving relates to the inverse square law of current.
Option B (50%) is the standard result for doubling the voltage in basic DC 2-wire distribution systems.
B is correct тАФ Doubling the supply voltage at a constant power reduces the conductor cross-section by half, leading to a 50% saving in the copper required for the distributor.
Always verify if the question assumes constant Power or constant Current; if Power is constant, current changes inversely to voltage, which is the key to solving transmission economics problems.