Join 60,000+ competitive exam aspirants
Voltages across the various disc of string of suspension insulator having identical discs is different due to
Surface leakage current
Series capacitance
Shunt capacitance to ground
Series and shunt capacitance
Shunt capacitance to ground
In a string of suspension insulators, the voltage distribution across each disc is non-uniform because the insulator units are not just connected to each other but also possess stray capacitances to the grounded metal tower structure. These shunt capacitances cause the charging current to increase as we move from the cross-arm towards the conductor, resulting in higher voltage stress on the disc nearest to the conductor.
In a string of suspension insulators, the voltage distribution across each disc is non-uniform because the insulator units are not just connected to each other but also possess stray capacitances to the grounded metal tower structure. These shunt capacitances cause the charging current to increase as we move from the cross-arm towards the conductor, resulting in higher voltage stress on the disc nearest to the conductor.
VnтАЛ=VnтИТ1тАЛ+InтИТ1тАЛ├ЧXcтАЛ тАФ recursive voltage drop equation
String┬аEfficiency=n├ЧVoltageacrossbottomdiscTotalvoltageacrossstringтАЛ
The metal pin and cap of each disc form a self-capacitance (C) between consecutive discs. Additionally, each metal link forms a shunt capacitance (CsтАЛ) to the grounded tower structure. Because of these shunt capacitances, the charging current flowing through the top unit is less than that flowing through the lower units, leading to uneven potential distribution where the unit closest to the line conductor experiences the maximum voltage.
The disc nearest to the conductor is always the most stressed.
String efficiency is always less than 100%.
String efficiency decreases as the number of discs in the string increases.
Grading of insulators (using different capacitance values) can improve uniformity.
Increased flexibility for high voltage lines
Easier maintenance and replacement of individual damaged discs
Non-uniform voltage distribution causes uneven electrical stress
Risk of puncture or flashover if the bottom disc exceeds its rated voltage
High voltage overhead transmission lines
Outdoor substation busbar support systems
Standard practice is to use a grading ring or corona ring at the bottom of the string to mitigate the effect of shunt capacitance.
Option B is incorrect because series capacitance is a deliberate design parameter, not the cause of the non-uniform distribution.
C is correct тАФ Shunt capacitance to ground causes the charging current to vary across the string, leading to non-uniform voltage distribution.
Remember that to improve string efficiency, the ratio of shunt capacitance to self-capacitance (k=CsтАЛ/C) should be kept as low as possible.