What should be the location of Lightning Arrester use for the protection of the Direct Lightning Strock?
At the highest high of the protecting equipment
Near the apparatus to be protected
At the entry and the exit of substation
All of these
At the highest high of the protecting equipment
To protect equipment from a direct lightning stroke, the lightning arrester or shielding mast/earth wire must be positioned at the highest point of the equipment or structure to be protected. Placing it at the highest elevated point ensures it intercepts the direct stroke high above the equipment and safely diverts the surge current to the ground before it can strike the main apparatus.
IS/IEC 62305 / IEEE Std 998
To protect equipment from a direct lightning stroke, the lightning arrester or shielding mast/earth wire must be positioned at the highest point of the equipment or structure to be protected. Placing it at the highest elevated point ensures it intercepts the direct stroke high above the equipment and safely diverts the surge current to the ground before it can strike the main apparatus.
R=hтЛЕtan(╬▒) тАФ Radius of protection cone at ground level
IpтАЛ=Z0тАЛ2VтАЛ тАФ Peak surge current generated by direct stroke
Direct lightning protection relies on the principle of shielding angle and electro-geometric model (rolling sphere method). By mounting the protective device (air terminal or arrester mast) at the apex, it provides a protective cone (typically 30┬░ to 45┬░) beneath it. Any incoming stepped leader attaches to the highest grounded point, discharging the high-impulse current safely to ground and preventing insulation breakdown of the underlying equipment.
Direct stroke protection requires interception at the highest physical apex before the stroke reaches the equipment.
The protection cone formed by an arrester/mast typically has a shielding angle (╬▒) of 30┬░ to 45┬░.
Surge arresters located near transformer terminals protect primarily against traveling waves (indirect strokes/surges), whereas direct protection relies on top-mounted shielding.
Intercepts high-energy direct lightning strokes before they hit vulnerable transformer or switchgear body.
Provides a defined zone of protection covering surrounding equipment within its shielding radius.
Requires robust low-resistance grounding to dissipate high impulse currents without causing back flashover.
Exposed to severe mechanical and thermal stresses during direct discharge.
Substation shielding masts and lightning rods.
Top structure mounting on high-voltage power transformers and transmission towers.
Direct stroke protection relies on shielding wires and top-mounted arresters/masts to divert the stroke directly to earth.
Option B refers to arresters used for protection against traveling waves originating from line switching or distant lightning (indirect protection).
A is correct тАФ The lightning arrester for direct stroke protection must be located at the highest height of the protected equipment to intercept the stroke first.
Distinguish between Direct Stroke Protection (uses overhead shield wires/masts at highest height) and Indirect/Surge Protection (uses line arresters connected as close as possible to transformer terminals).