Which system will need the lightning arrester of least voltage rating?
Solid ground neutral system
Insulated neutral system
Resistance grounded neutral system
Reactance grounded neutral system
Solid ground neutral system
In a solid ground neutral system (effectively grounded system), the voltage of the healthy phases during a single line-to-ground (LG) fault does not exceed 0.8 times (or 80%) of the line-to-line voltage, keeping the Coefficient of Earthing (CoE) тЙд80%. Because the healthy phase voltage rise is minimal during ground faults, the continuous operating voltage and transient overvoltages are lowest, allowing a lightning arrester of the least voltage rating to be used.
IEEE C62.22 / IS 3043:2018
In a solid ground neutral system (effectively grounded system), the voltage of the healthy phases during a single line-to-ground (LG) fault does not exceed 0.8 times (or 80%) of the line-to-line voltage, keeping the Coefficient of Earthing (CoE) тЙд80%. Because the healthy phase voltage rise is minimal during ground faults, the continuous operating voltage and transient overvoltages are lowest, allowing a lightning arrester of the least voltage rating to be used.
CoE=Vline-lineтАЛVhealthy-groundтАЛтАЛ├Ч100% тАФ Coefficient of Earthing
VarresterтАЛтЙеCoE├ЧVsystem(line-line)тАЛ тАФ Voltage rating requirement for surge arrester
X1тАЛX0тАЛтАЛтЙд3andX1тАЛR0тАЛтАЛтЙд1 тАФ Condition for an effectively (solidly) grounded system
When a single line-to-ground fault occurs in an ungrounded or high-impedance grounded system, the voltage of the healthy phases rises to the full line-to-line voltage (a 3тАЛ or 173.2% increase). In contrast, solid grounding anchors the neutral point firmly to ground potential, suppressing power-frequency overvoltages on healthy phases during an LG fault. Consequently, the maximum continuous operating voltage (MCOV) and duty requirement for surge arresters connected from line to ground are significantly lower.
Solid grounding makes a system 'effectively grounded', restricting healthy phase voltage under ground faults to 80% of phase-to-phase voltage.
A lower power-frequency voltage during faults permits fitting lightning arresters with reduced rated voltage and continuous operating voltage (MCOV).
Lower rating of lightning arrester directly reduces costs and improves the protective margin for downstream equipment like transformers.
Reduces cost and size of lightning arresters due to lower voltage rating requirement.
Provides better protective margin and insulation coordination for substation equipment.
Eliminates arcing grounds and severe transient overvoltages.
Produces high single line-to-ground fault currents, leading to greater mechanical stress on equipment.
Increases potential severe severe interference with nearby communication lines during ground faults.
High Voltage (HV) and Extra High Voltage (EHV/UHV) transmission networks (> 66 kV).
Substation power transformer neutral grounding where cost savings on surge arresters and insulation are critical.
In an isolated/insulated neutral system, healthy phases experience full line-to-line voltage during an LG fault (100% rating arrester required).
Resistance and reactance grounded neutral systems limit fault current but allow healthy phase voltage to rise higher than solid grounding, requiring higher-rated surge arresters.
A is correct тАФ Solid ground neutral system limits the healthy phase voltage rise under ground faults to 80% of line voltage, allowing the lowest lightning arrester rating.
For competitive exams, remember: Solid grounding тЖТ Lowest Arrester Rating (80%) & Highest Fault Current; Insulated Neutral тЖТ Highest Arrester Rating (100%) & Arcing Ground Risk.