When a transformer is loaded, the secondary terminal voltage gains. That means the load Power factor is
Zero
Leading
Unity
Lagging
Leading
When a transformer delivers a leading power factor load, the secondary terminal voltage increases relative to the no-load voltage due to the Ferranti-like effect caused by the interaction of leakage reactance and capacitive load current. This phenomenon is characterized by a negative voltage regulation, where the reactive voltage drop I2тАЛ(R2тАЛcos╧Х2тАЛтИТX2тАЛsin╧Х2тАЛ) becomes negative.
When a transformer delivers a leading power factor load, the secondary terminal voltage increases relative to the no-load voltage due to the Ferranti-like effect caused by the interaction of leakage reactance and capacitive load current. This phenomenon is characterized by a negative voltage regulation, where the reactive voltage drop I2тАЛ(R2тАЛcos╧Х2тАЛтИТX2тАЛsin╧Х2тАЛ) becomes negative.
VRтАЛ=V2тАЛE2тАЛтИТV2тАЛтАЛ├Ч100 тАФ Percentage Voltage Regulation
V2тАЛтЙИE2тАЛтИТI2тАЛ(Re2тАЛcos╧Х2тАЛтИТXe2тАЛsin╧Х2тАЛ) тАФ Approximate secondary voltage for leading PF
The transformer secondary voltage V2тАЛ is governed by the equation V2тАЛ=E2тАЛтИТI2тАЛ(Re2тАЛ+jXe2тАЛ). For a leading power factor, the current I2тАЛ leads the terminal voltage. The internal voltage drop I2тАЛX2тАЛ acts in a direction that opposes the inductive drop, resulting in a resultant voltage magnitude that can exceed the induced EMF E2тАЛ.
Leading power factor loads result in negative voltage regulation.
The secondary terminal voltage rises above the no-load voltage when the capacitive effect dominates.
Unity power factor yields the minimum voltage drop for inductive-resistive circuits.
Lagging power factor always results in a significant voltage drop.
Used in VAR compensation studies.
Helps in understanding resonance conditions in power systems.
May lead to overvoltage conditions in distribution lines.
Requires careful insulation coordination.
Power system stability studies.
Design of reactive power compensators.
Negative regulation occurs only when sin╧Х2тАЛ is positive and sufficient to outweigh the resistive drop.
For lagging loads, the term (Re2тАЛcos╧Х2тАЛ+Xe2тАЛsin╧Х2тАЛ) is positive, leading to a drop in terminal voltage.
B is correct тАФ A transformer exhibits a rise in secondary terminal voltage under load when the load power factor is leading due to negative voltage regulation.
Always remember the mnemonic: 'Leading load leads to a rise, lagging load leads to a drop' regarding transformer terminal voltage.