Whenever the conductors are dead-ended or there is a change in the direction of transmission line, the insulators used are of the
Pin type
Suspension type
Strain type
Shackle type
Strain type
Strain insulators are designed to withstand the high mechanical tension that occurs at dead-end points or where transmission lines change direction. Unlike suspension or pin insulators, which primarily support the conductor weight, strain insulators are placed in series with the conductor to handle axial mechanical pull.
Strain insulators are designed to withstand the high mechanical tension that occurs at dead-end points or where transmission lines change direction. Unlike suspension or pin insulators, which primarily support the conductor weight, strain insulators are placed in series with the conductor to handle axial mechanical pull.
TmaxтАЛ=Maximum┬аtension┬аat┬аdead-end
NтЛЕIsтАЛтЙеTmaxтАЛ тАФ where N is the number of strings and IsтАЛ is the strength per insulator
When a transmission line reaches a terminal tower or a dead-end, the tension in the conductor creates a large longitudinal force. To handle this, the conductor is anchored using strain insulators mounted horizontally or in a string, ensuring the mechanical load is decoupled from the support structure while maintaining necessary electrical insulation.
Used at dead-end towers, sharp turns, and long spans.
Mechanical strength is the primary design requirement compared to electrical stress.
Usually installed in a horizontal position for high voltage transmission lines.
High mechanical strength to handle line tension.
Reduces mechanical load on the transmission tower structure.
Provides reliable isolation at termination points.
More expensive than simple pin insulators.
Requires more physical space for installation at turning angles.
Terminal poles and dead-end towers.
Transmission line angle supports.
River crossing spans where tension is extremely high.
For voltages above 11 kV, suspension type insulators are often used as strain insulators by installing them in a horizontal string.
Pin insulators are only suitable for straight sections up to 33 kV and cannot handle the longitudinal tension of a dead-end.
C is correct тАФ Strain type insulators are specifically engineered to endure the high axial mechanical tension experienced at dead-ends and angular changes in overhead transmission lines.
Always remember: if the question mentions 'mechanical tension' or 'dead-end', the answer is almost always 'Strain Insulator'.