Which equipment is used for EHV lines to improve power transferability?
Shunt capacitor
Shunt reactor
Series capacitor
All of these
Series capacitor
Series capacitors are connected in series with the transmission line to provide negative reactance, which partially cancels out the positive inductive reactance of the line. This reduction in the total effective reactance (XeffтАЛ=XLтАЛтИТXCтАЛ) significantly increases the steady-state power transfer capability of long EHV transmission lines.
Series capacitors are connected in series with the transmission line to provide negative reactance, which partially cancels out the positive inductive reactance of the line. This reduction in the total effective reactance (XeffтАЛ=XLтАЛтИТXCтАЛ) significantly increases the steady-state power transfer capability of long EHV transmission lines.
P=XLтАЛтИТXCтАЛVSтАЛVRтАЛтАЛsin╬┤ тАФ Power transfer equation with series compensation
XeffтАЛ=XLтАЛтИТXCтАЛ тАФ Net effective reactance of the compensated line
The power transfer equation for a lossless transmission line is given by P=XVSтАЛVRтАЛтАЛsin╬┤. By inserting a series capacitor, the line reactance X is reduced to XLтАЛтИТXCтАЛ, thereby increasing the maximum power transfer capacity for the same voltage profile and angular displacement ╬┤. It also enhances system stability by reducing the voltage drop and improving the power angle characteristic.
Series capacitors reduce the inductive reactance of long transmission lines.
They are primary tools for increasing the static stability limit of power systems.
Sub-synchronous resonance (SSR) is a critical technical concern when using series compensation.
Used mainly for lines longer than 300-400 km where inductive reactance dominates.
Increases the power transfer capability of existing lines.
Improves system voltage regulation under load conditions.
Enhances transient stability limits.
Possibility of Sub-synchronous Resonance (SSR) with turbine-generators.
Requires high-voltage insulation and protection equipment (spark gaps/varistors).
Complicated relaying and protection schemes due to fault current characteristics.
Long-distance EHV and UHV transmission lines.
Systems requiring improved power sharing between parallel lines.
Dynamic stability support in interconnected grids.
Shunt reactors (Option B) are used to compensate for the Ferranti effect in lightly loaded lines and to control overvoltages, but they reduce power transfer capacity.
Shunt capacitors (Option A) are used for voltage support and power factor correction, not for increasing series reactance-based power transfer.
C is correct тАФ Series capacitors reduce the net inductive reactance of the transmission line, thereby directly increasing the power transfer limit as defined by the power-angle equation.
Always remember that Series components (XCтАЛ in series) affect the line's impedance properties for power flow, while Shunt components (XCтАЛ or XLтАЛ in shunt) are primarily used for voltage regulation.