Which among these is a configuration of an isolator? i. Vertical break type ii. Horizontal type iii. Horizontal break with two post insulator iv. Horizontal break centre post rotating double break v. Pantograph type
Only ii and iii
i, ii, iii, and iv
i, ii, iii, iv, v
i, ii, iv, v
i, ii, iii, iv, v
An isolator (or disconnecting switch) is an off-load mechanical switching device used to isolate a part of an electrical power system for maintenance or safety. Isolators are manufactured in various mechanical configurations depending on voltage level, space availability, and clearance requirements. All listed options (Vertical break, Horizontal break, Horizontal break with two post insulators, Horizontal break center post rotating double break, and Pantograph type) are standard commercial configurations of isolators used in substations.
IS 9921 / IEC 62271-102
An isolator (or disconnecting switch) is an off-load mechanical switching device used to isolate a part of an electrical power system for maintenance or safety. Isolators are manufactured in various mechanical configurations depending on voltage level, space availability, and clearance requirements. All listed options (Vertical break, Horizontal break, Horizontal break with two post insulators, Horizontal break center post rotating double break, and Pantograph type) are standard commercial configurations of isolators used in substations.
IcapacityтАЛ=0┬аA┬а(Off-load┬аoperation┬аrequired) тАФ breaking capacity under normal conditions
VlineтАЛтЙе11┬аkV┬аto┬а765┬аkV тАФ voltage range for isolator deployment
Isolators operate under no-load conditions to ensure safety by providing a visible physical break in the circuit. The switching mechanism is driven manually or via a motorized gang-operated drive shaft that rotates or lifts the insulator posts to disengage the contacts. Pantograph isolators operate vertically to save horizontal substation bay width at extra-high voltages.
Isolators are strictly off-load switching devices operated only after circuit breakers open.
Vertical break isolators require less horizontal clearance between phases.
Double break isolators feature three insulator posts per phase, where the central post rotates.
Pantograph isolators are preferred in EHV/UHV substations (220┬аkV, 400┬аkV, 765┬аkV) to minimize substation footprint.
Provides a visible and safe isolation gap for maintenance personnel.
Pantograph designs significantly reduce overall substation ground area.
Simple mechanical construction with high reliability and low maintenance.
Zero arc-quenching capability; cannot interrupt load or fault currents.
Risk of severe flashover if operated inadvertently on-load.
Isolation of transformers, busbars, and transmission line sections in outdoor substations.
Earthing switch integration for grounding isolated lines during maintenance.
Isolators are interlocked with Circuit Breakers and Earth Switches to prevent accidental on-load operation (Interlocking sequence: Open CB тЖТ Open Isolator тЖТ Close Earth Switch).
Options i, ii, iii, iv, and v are all standard engineering classifications of substation isolators.
C is correct тАФ All listed types (i, ii, iii, iv, and v) represent standard physical and operational configurations of electrical isolators used in power substations.
Remember the switching order for exams: to de-energize, open Circuit Breaker first, then open Isolator, then close Earth Switch. To energize, perform the exact reverse.