Which of the following losses in the transformer varies with load?
Copper loss
Eddy current loss
Hysteresis loss
Stray loss
Copper loss
Copper losses, also known as I┬▓с┤┐ losses, are dependent on the current flowing through the transformer windings. As the load on the transformer increases, the current drawn by the secondary (and consequently primary) increases, causing these losses to vary quadratically with the load.
Copper losses, also known as I┬▓с┤┐ losses, are dependent on the current flowing through the transformer windings. As the load on the transformer increases, the current drawn by the secondary (and consequently primary) increases, causing these losses to vary quadratically with the load.
PcuтАЛ=I2R тАФ Calculation of Copper loss based on winding resistance and current
PtotalтАЛ=PcoreтАЛ+x2Pfull_loadтАЛ тАФ Total transformer loss at load fraction x
In a transformer, the primary and secondary windings have a specific resistance R. According to Joule's law of heating, the power dissipated as heat in a resistor is P=I2R. Since the load current I2тАЛ is proportional to the output power demanded by the load, the copper loss varies as the square of the load current (PcuтАЛтИЭI2).
Copper losses are 'variable' losses, while Hysteresis and Eddy current losses are 'constant' (core) losses.
Copper losses increase by the square of the load factor.
At full load, copper losses are maximum; at no load, they are approximately zero.
Used to determine the efficiency of the transformer at different loading conditions.
Helpful in designing thermal cooling systems for transformers.
High copper losses lead to excessive heating, reducing transformer insulation life.
Decreases overall transformer efficiency under heavy load conditions.
Transformer efficiency calculation.
Determination of All-Day Efficiency.
Voltage regulation calculations.
Eddy current and Hysteresis losses depend primarily on the flux density and supply frequency, which remain constant in a constant voltage transformer.
Option B (Eddy Current) and Option C (Hysteresis) are categorized as Core or Iron losses.
A is correct тАФ Copper losses are directly proportional to the square of the load current.
Remember that iron losses are constant, so at the point of maximum efficiency, the variable copper loss exactly equals the constant iron loss.