What will be the hysteresis loss if the supply frequency of a transformer becomes double?
Eight times
Four times
Doubled
Remains the same
Doubled
Hysteresis loss is directly proportional to the supply frequency when the magnetic flux density (BmтАЛ) is kept constant. If the frequency of the supply is doubled while maintaining constant voltage (and thus constant flux per pole), the hysteresis loss also doubles.
Hysteresis loss is directly proportional to the supply frequency when the magnetic flux density (BmтАЛ) is kept constant. If the frequency of the supply is doubled while maintaining constant voltage (and thus constant flux per pole), the hysteresis loss also doubles.
PhтАЛ=╬╖Bm1.6тАЛfV тАФ Steinmetz hysteresis loss equation
PhтАЛтИЭf тАФ Proportionality when flux density is constant
Hysteresis loss arises from the energy dissipated as heat due to the friction of magnetic domains within the transformer core during the process of magnetization and demagnetization. According to Steinmetz's empirical formula, PhтАЛ=╬╖Bm1.6тАЛfV. Since BmтАЛтИЭfVтАЛ, in a scenario where voltage is adjusted to keep flux constant or where the ratio is analyzed, the loss exhibits a linear relationship with frequency f.
Hysteresis loss depends on the magnetic properties of the core material (Steinmetz coefficient ╬╖).
It is proportional to the area of the B-H loop.
Higher frequency means more cycles of magnetization per second, leading to higher heat dissipation.
Eddy current loss is proportional to f2, which behaves differently than hysteresis loss.
Provides a clear relationship between magnetic core behavior and frequency
Helps in designing high-frequency transformers to minimize core losses
Assumes constant maximum flux density which may not be true in all field conditions
Does not account for non-linear saturation effects at very high frequencies
Transformer design and efficiency optimization
Selection of magnetic materials (CRGO steel) for transformer cores
In practice, the relation PhтАЛтИЭf holds only if the flux density BmтАЛ remains constant (i.e., V/f ratio is constant).
Option B (Four times) is incorrect because that would apply to Eddy Current loss, which is proportional to f2.
C is correct тАФ Hysteresis loss is directly proportional to frequency, so doubling the frequency results in a doubling of the loss.
Remember that Eddy Current loss is proportional to f2, whereas Hysteresis loss is proportional to f1.