Which of the following statement is correct?
Ice on conductor increases the skin effect
Wind pressure reduces the corona effect
Wind pressure is taken to act at perpendicular to that of ice
Ice on conductors reduces sag
Wind pressure is taken to act at perpendicular to that of ice
In overhead transmission line design, mechanical loading is calculated by considering the vector sum of ice weight (acting vertically downward) and wind force (acting horizontally). Since these two loads act in perpendicular directions, the resultant total load is calculated using the Pythagorean theorem.
In overhead transmission line design, mechanical loading is calculated by considering the vector sum of ice weight (acting vertically downward) and wind force (acting horizontally). Since these two loads act in perpendicular directions, the resultant total load is calculated using the Pythagorean theorem.
wrтАЛ=(wcтАЛ+wiтАЛ)2+ww2тАЛтАЛ тАФ Resultant load per unit length
╬╕=tanтИТ1(wcтАЛ+wiтАЛwwтАЛтАЛ) тАФ Angle of the resultant load with vertical
When calculating the sag of a transmission line under adverse weather conditions, we consider the weight of the conductor (wcтАЛ), the weight of ice (wiтАЛ), and the force due to wind pressure (wwтАЛ). The wind pressure is exerted on the projected area of the conductor perpendicular to the conductor axis, while gravity and ice act vertically. The effective vertical load becomes (wcтАЛ+wiтАЛ) and the horizontal load is (wwтАЛ). The resultant load (wrтАЛ) is (wcтАЛ+wiтАЛ)2+ww2тАЛтАЛ, which acts at an angle to the vertical.
Ice loading increases the effective weight of the conductor, thereby increasing the sag.
Wind pressure increases the total resultant force, which typically increases the sag if the horizontal component dominates.
The sag (S) is directly proportional to the total resultant weight (S=8TwrтАЛl2тАЛ).
Option A is incorrect because ice increases the effective diameter, which generally increases the corona effect (due to surface irregularity), but it does not specifically define the skin effect behavior in that context.
Option B is incorrect because wind pressure does not reduce the corona effect; if anything, increased effective conductor diameter might marginally reduce corona, but it is not the standard design rule.
Option D is incorrect because ice significantly increases the vertical weight, leading to a substantial increase in sag, not a reduction.
C is correct тАФ Wind pressure acts on the projected area of the conductor in a direction perpendicular to the conductor axis, which is orthogonal to the vertical gravitational force of the ice.
Always remember that sag (S=8TwL2тАЛ) is proportional to the resultant load (wrтАЛ); hence, any accumulation of ice increases both the weight and the resulting sag significantly.