Zero sequence currents can flow from a line into a transformer bank if the windings are in
Grounded star/delta
Delta/star
Star/grounded star
Delta/delta
Grounded star/delta
Zero sequence currents (I0тАЛ) can only flow in a transformer winding if there is a physical path for the current to return to the neutral. A grounded star winding provides this return path, while a delta winding provides a circulating path for zero sequence currents without needing a ground connection, thus allowing them to flow from the line.
Zero sequence currents (I0тАЛ) can only flow in a transformer winding if there is a physical path for the current to return to the neutral. A grounded star winding provides this return path, while a delta winding provides a circulating path for zero sequence currents without needing a ground connection, thus allowing them to flow from the line.
I0тАЛ=31тАЛ(IaтАЛ+IbтАЛ+IcтАЛ) тАФ Zero sequence component definition
NpтАЛI0pтАЛ=NsтАЛI0sтАЛ тАФ Ampere-turn balance for zero sequence currents
The zero sequence current is defined as I0тАЛ=31тАЛ(IaтАЛ+IbтАЛ+IcтАЛ). In a grounded star-delta transformer, the grounded star point allows the zero sequence current to enter from the system to the windings. On the secondary (delta) side, this current induces a circulating zero sequence current that flows within the closed loop of the delta, effectively satisfying the ampere-turn balance (N1тАЛI0тАЛ=N2тАЛI0,deltaтАЛ) required for transformer operation.
Zero sequence currents cannot flow in an ungrounded star system because the sum of line currents must be zero.
A delta connection acts as a trap or circulation path for zero sequence currents, preventing them from propagating into the supply side if the transformer is Delta-Delta or Star-Delta.
Grounded star configuration is essential for zero sequence current circulation between the line and the transformer.
Allows detection of ground faults by sensitive earth-fault relays.
Limits zero sequence voltage rise during unsymmetrical faults.
Increased stress on transformer windings during line-to-ground faults.
Potential for circulating currents to cause localized heating in delta windings.
Transmission and distribution substations.
Grounding transformers (Zig-zag transformers).
In a Delta/Delta transformer, there is no path for zero sequence current to flow to the ground from the line, making it 'zero-sequence blocking'.
Option B (Delta/star) behaves similarly to A if the star point is grounded, but usually, the 'from a line into' phrasing specifically tests the grounding aspect of the primary/source side.
A is correct тАФ The grounded star connection provides the necessary path for zero sequence currents to flow from the line into the transformer.
Remember: The presence of a delta winding is required to provide a path for circulating zero sequence currents, but a grounded star point is required to allow those currents to enter the transformer from the line side.