A coal-fired steam power station working at a plant load factor of 80% has one 500 MW generating unit. If the heat content of coal is 2 kWh/kg, the overall plant efficiency is 40% and a train load of coal is 2,000 metric tons, then the number of trains required daily for the plant is
10
24
A is correct because the daily coal requirement is 12,000 metric tons, which necessitates 6 trains daily (Note: The provided options in the prompt appear to be missing the correct value '6').
Plant Capacity = 500 MW, Plant Load Factor = 80%, Heat content of coal = 2 kWh/kg, Overall Efficiency = 40%, Train load = 2,000 metric tons
Daily┬аEnergy=Capacity├ЧLoadFactor├Ч24,Fuel┬аRequired=Efficiency├ЧHeatContentDailyEnergyтАЛ,Trains=TrainLoadFuelRequiredтАЛ
Calculate Daily Energy Produced
The actual energy generated daily is the product of rated capacity, load factor, and hours in a day.
E=500├Ч103┬аkW├Ч0.8├Ч24┬аh=9.6├Ч106┬аkWh
Calculate Fuel Energy Required
Considering the overall plant efficiency of 40%, the thermal energy input required is higher than the electrical output.
QinтАЛ=╬╖EтАЛ=0.49.6├Ч106тАЛ=24├Ч106┬аkWh
Calculate Mass of Coal Required
Given the coal heat content is 2 kWh/kg, convert thermal energy to coal mass in kg.
M=2┬аkWh/kg24├Ч106┬аkWhтАЛ=12├Ч106┬аkg=12,000┬аmetric┬аtons
Calculate Number of Trains
Divide the total daily coal requirement by the capacity of a single train load.
N=2,000┬аmetric┬аtons/train12,000┬аmetric┬аtonsтАЛ=6
A is correct because the daily coal requirement is 12,000 metric tons, which necessitates 6 trains daily (Note: The provided options in the prompt appear to be missing the correct value '6').
In power systems, the relationship between thermal input and electrical output is defined by the heat rate, which is the reciprocal of the product of efficiency and calorific value.