Join 60,000+ competitive exam aspirants
A three-phase, 50 Hz transmission line has a capacitance of line to neutral Cₙ = 0.01 μF/km. The voltage of the line is 100 kV. The charging current per kilometer of line is
314/3 A/km
314/(3×103) A/km
(3×103)/314 A/km
(3×103) A/km
314/(3×103) A/km
B is correct because the charging current calculation using the phase-to-neutral voltage yields 314/(3×103) A/km.
Three-phase line voltage VL = 100 kV, Frequency f = 50 Hz, Capacitance Cn = 0.01 μF/km
Ic=2πfCnVph=2πfCn3VL
Identify phase voltage
Since it is a three-phase system, the charging current per unit length depends on the phase-to-neutral voltage. Given line voltage VL=100×103 V, the phase voltage Vph is:
Vph=3100×103 V
Calculate angular frequency
The angular frequency ω is related to supply frequency f by ω=2πf. Given f=50 Hz:
ω=2×π×50=100π=314 rad/s
Calculate charging current
The charging current per kilometer is Ic=ωCnVph. Substituting Cn=0.01×10−6 F/km and other values:
Ic=314×(0.01×10−6)×3100×103
Simplify expression
Simplifying the numerical values: 314×0.01×100=314. Including the powers of ten: 10−6×103=10−3=1031. Thus, the final form is:
Ic=3×103314 A/km
B is correct because the charging current calculation using the phase-to-neutral voltage yields 314/(3×103) A/km.
In power systems, always distinguish between line-to-line voltage and phase-to-neutral voltage when calculating capacitive effects in three-phase transmission lines.