If a synchronous machine is under excited it takes lagging VAR from the system when it is operated as a
Synchronous motor
Synchronous generator
Synchronous motor as well as generator
None of the above
Synchronous motor as well as generator
An under-excited synchronous machine, whether operating as a motor or generator, fails to produce sufficient reactive power to meet its own internal magnetization requirements. Consequently, it draws lagging reactive power (VAR) from the connected power system to maintain the air-gap flux.
An under-excited synchronous machine, whether operating as a motor or generator, fails to produce sufficient reactive power to meet its own internal magnetization requirements. Consequently, it draws lagging reactive power (VAR) from the connected power system to maintain the air-gap flux.
Q=XsтАЛVтАЛ(Ecos╬┤тИТV) тАФ Reactive power equation for synchronous machine
Q<0 тАФ Condition for absorbing lagging VAR (under-excited)
In a synchronous machine, the reactive power exchange is governed by the excitation level relative to the terminal voltage. If the excitation (field current) is low, the back EMF (EbтАЛ) or generated voltage (EgтАЛ) is lower than the terminal voltage (V). To satisfy the magnetic flux requirements, the machine acts as an inductive load and consumes lagging reactive power from the AC source.
Under-excited machine behaves like an inductor (absorbs lagging VAR).
Over-excited machine behaves like a capacitor (supplies lagging VAR/absorbs leading VAR).
The excitation level is defined by the field current IfтАЛ relative to the rated excitation.
Synchronous motors are often used for power factor correction when over-excited.
Capability to control voltage by adjusting excitation.
Variable power factor operation.
Risk of loss of synchronism if excitation is too low.
Increased heating due to reactive current flow.
Synchronous condensers for voltage regulation.
Industrial drives requiring precise speed control.
An under-excited synchronous generator is susceptible to instability and steady-state limit violations.
The term 'taking lagging VAR' is equivalent to 'delivering leading VAR' to the system.
C is correct тАФ Both synchronous motors and generators consume lagging reactive power when operated in the under-excited mode, regardless of whether they are converting electrical to mechanical energy or vice versa.
Always remember the V-Curve mnemonic: Under-excited = Inductive/Lagging-Absorption; Over-excited = Capacitive/Leading-Absorption.