If the separation between three phases of a transmission line is increased then
Inductance will increase and capacitance will remain unchanged
Both the inductance and capacitance will increase
Inductance will increase and capacitance will decrease
Inductance will decrease and capacitance will increase
Inductance will increase and capacitance will decrease
In a three-phase transmission line, the inductance is directly proportional to the logarithm of the geometric mean distance (GMD) between conductors, while capacitance is inversely proportional to the logarithm of the GMD. Increasing the separation distance increases the GMD, leading to an increase in loop inductance and a decrease in shunt capacitance.
In a three-phase transmission line, the inductance is directly proportional to the logarithm of the geometric mean distance (GMD) between conductors, while capacitance is inversely proportional to the logarithm of the GMD. Increasing the separation distance increases the GMD, leading to an increase in loop inductance and a decrease in shunt capacitance.
L=2├Ч10тИТ7ln(GMRGMDтАЛ)┬аH/m тАФ Inductance per phase
C=ln(GMD/r)2╧А╧╡0тАЛтАЛ┬аF/m тАФ Capacitance per phase
The inductance of a conductor is determined by the magnetic flux linkage. As separation increases, the flux linkage per unit current increases due to the larger loop area, raising the inductance. Conversely, capacitance is determined by the electric field distribution; increasing the distance between conductors reduces the flux density and potential gradient for a given voltage, thereby decreasing the capacitance per unit length.
Inductance depends on the magnetic flux linkages and increases with larger spacing.
Capacitance depends on the stored electric charge and decreases as spacing increases.
GMD (Geometric Mean Distance) represents the effective spacing between phase conductors.
Changes in spacing affect the surge impedance Z0тАЛ=CLтАЛтАЛ, which typically increases with separation.
Increased spacing reduces the probability of phase-to-phase faults.
Reduced capacitance minimizes the Ferranti effect in lightly loaded or unloaded lines.
Increased inductance leads to higher voltage drops under heavy load conditions.
Larger tower structures are required to maintain the increased physical separation.
High Voltage (HV) and Extra High Voltage (EHV) transmission line design.
Optimization of line surge impedance loading (SIL).
The GMD is calculated as 3DabтАЛDbcтАЛDcaтАЛтАЛ for an untransposed line.
Option A is incorrect because capacitance changes significantly with separation distance.
Option D is incorrect as it describes the inverse of the actual physical behavior.
C is correct тАФ Increasing the separation between transmission line phases increases the inductance due to larger flux linkage and decreases the capacitance due to reduced field coupling.
Always remember that for transmission lines, L and C are inverse functions of the spacing logarithm; use this to quickly identify the effect on surge impedance.