Installation of capacitors at suitable locations and of optimum size in a distribution system results in
improved voltage regulation
reduction in distribution power losses
reduction of kVA rating of distribution transformers
Select the correct answer from the codes given below
and 2
1, 2 and 3
alone
1, 2 and 3
The installation of capacitors in a distribution system compensates for the reactive power demand of inductive loads, leading to an increase in power factor and a reduction in the total current drawn from the source. This optimization directly improves voltage regulation, reduces ohmic power losses (I2R), and decreases the total MVA load on transformers.
The installation of capacitors in a distribution system compensates for the reactive power demand of inductive loads, leading to an increase in power factor and a reduction in the total current drawn from the source. This optimization directly improves voltage regulation, reduces ohmic power losses (I2R), and decreases the total MVA load on transformers.
PlossтАЛтИЭI2R тАФ relationship between current and power loss
PF=cos╧Х=SPтАЛ тАФ definition of power factor
In a distribution system, most loads are inductive, causing the current to lag behind the voltage. By placing capacitors in parallel, the capacitive reactive power (QcтАЛ) supplies the inductive reactive power (QLтАЛ) locally, reducing the net reactive power (QnetтАЛ=QLтАЛтИТQcтАЛ) that must flow through the transmission and distribution lines. Since S=P2+Qnet2тАЛтАЛ, decreasing QnetтАЛ lowers the apparent power (S) required from the transformer and reduces line current I, which scales linearly with S.
Voltage regulation improves because lower current reduces the voltage drop across line impedance (VdropтАЛтЙИI(Rcos╧Х+Xsin╧Х)).
Transformer capacity utilization increases, effectively releasing dormant kVA capacity.
Reduction in I minimizes heating effects in cables and conductors.
Optimum sizing prevents over-compensation, which could lead to an undesirable rise in voltage (Ferranti effect at distribution level).
Reduced energy billing costs (for industrial consumers)
Increased system capacity
Improved voltage stability
High initial investment cost
Requires maintenance and switching control
Potential for harmonics resonance
Industrial motor loads
Utility substation distribution buses
Commercial complexes with heavy inductive loads
Most electrical utilities incentivize high power factor to reduce system stress.
Option D is incorrect as it only focuses on one benefit; points 1, 2, and 3 are all technically correct consequences of shunt capacitor application.
C is correct тАФ Installation of capacitors improves power factor, which simultaneously optimizes voltage, reduces power losses, and frees up transformer kVA capacity.
Always remember that shunt capacitors decrease total current flow, which creates a 'triple-win' scenario: better voltage, lower thermal losses, and increased effective transformer capacity.