Internal flux linkage due to internal flux of a conductor is
I├Ч10тИТ7 Wb-T/m
0.25I├Ч10тИТ7 Wb-T/m
0.5I├Ч10тИТ7 Wb-T/m
0.5├Ч10тИТ7 Wb-T/m
0.5I├Ч10тИТ7 Wb-T/m
The internal flux linkage per unit length of a solid cylindrical conductor carrying current I is constant, regardless of the conductor radius. It is given by 8╧А╬╝0тАЛIтАЛ Weber-turns per meter, which simplifies to 0.5├Ч10тИТ7I Wb-T/m.
The internal flux linkage per unit length of a solid cylindrical conductor carrying current I is constant, regardless of the conductor radius. It is given by 8╧А╬╝0тАЛIтАЛ Weber-turns per meter, which simplifies to 0.5├Ч10тИТ7I Wb-T/m.
╬╗intтАЛ=8╧А╬╝0тАЛIтАЛ тАФ internal flux linkage per unit length
LintтАЛ=8╧А╬╝0тАЛтАЛ=0.5├Ч10тИТ7 H/m тАФ internal inductance per unit length
When a current flows through a conductor, magnetic flux is produced both inside and outside the conductor. The flux inside the conductor is non-uniform, as it only links a fraction of the total current. By integrating the flux density BxтАЛ from the center to the surface of the conductor (radius r), we derive the effective internal inductance LintтАЛ=8╧А╬╝0тАЛтАЛ H/m, which yields the internal flux linkage as LintтАЛ├ЧI.
Internal flux linkage is independent of the radius of the conductor.
The internal flux linkage value is constant for any non-magnetic solid cylindrical conductor.
mu0тАЛ is the permeability of free space, approximately 4╧А├Ч10тИТ7 H/m.
Simplifies calculation of transmission line impedance parameters.
Allows for easy estimation of conductor internal reactance at power frequencies.
Applicable only to solid cylindrical conductors (not stranded or hollow conductors).
Assumes uniform current distribution (DC or low-frequency assumption).
Calculation of GMR (Geometric Mean Radius).
Transmission line parameter modeling.
The value is derived from the magnetic field strength HxтАЛ=2╧Аr2IxтАЛ at a distance x from the center.
Option D is incorrect because it misses the current factor I in the numerator, as flux linkage must be proportional to current.
C is correct тАФ The internal flux linkage of a conductor is mathematically derived as 0.5├Ч10тИТ7I Wb-T/m.
Remember that external flux linkage depends on the distance from the conductor, whereas internal flux linkage is a constant value of 0.5├Ч10тИТ7I for solid wires.