The best place to install a capacitor is
very near to inductive load
across the terminals of inductive load
far away from the inductive load
any where
across the terminals of inductive load
The optimal installation point for power factor correction capacitors is directly across the terminals of the inductive load. This configuration minimizes the circulation of reactive current throughout the distribution wiring, significantly reducing I2R losses and voltage drops.
The optimal installation point for power factor correction capacitors is directly across the terminals of the inductive load. This configuration minimizes the circulation of reactive current throughout the distribution wiring, significantly reducing I2R losses and voltage drops.
QCтАЛ=P(tan╧Х1тАЛтИТtan╧Х2тАЛ) тАФ Required reactive power of capacitor to improve PF from cos╧Х1тАЛ to cos╧Х2тАЛ
ItotalтАЛ=IR2тАЛ+(ILтАЛтИТICтАЛ)2тАЛ тАФ Total line current with compensation
Inductive loads (like motors) draw lagging reactive current (ILтАЛ) from the supply, which lowers the overall power factor. By placing a capacitor in parallel, the capacitor provides a leading reactive current (ICтАЛ) locally at the load terminals. This results in the cancellation of the magnetizing current component, meaning the supply lines only carry the active power current (IPтАЛ), effectively improving the power factor at the source.
Reduces current drawn from the utility grid.
Decreases power losses in transmission and distribution cables (PlossтАЛтИЭI2).
Improves voltage regulation at the load end.
Prevents penalties for low power factor in industrial tariff structures.
Lower line current leads to smaller wire sizes and less heating.
Better utilization of transformer and generator KVA capacity.
Reduced electricity bills due to improved PF.
High initial cost for high-capacity capacitor banks.
Potential for over-correction leading to leading power factor at light loads.
Harmonic resonance risk if capacitors interact with system inductance.
Industrial induction motors
Power distribution transformers
Welding machines and arc furnaces
Installing capacitors at the load end is known as 'Individual Compensation'.
Installing at the main distribution board is 'Group Compensation', and at the substation is 'Central Compensation'.
Options A and C are technically inferior because they do not prevent reactive current flow in the feeder cables between the load and the capacitor.
B is correct тАФ Placing capacitors across the terminals of the inductive load ensures that reactive power is neutralized at the point of origin, maximizing efficiency.
Always remember: for maximum system efficiency, compensate reactive power as close to the load as physically possible to minimize 'I' in the I2R loss equation across the distribution lines.