The charging reactance of 50 km length of line is 1500 Ω. The charging reactance for 100 km length of line will be
1500 Ω
3000 Ω
750 Ω
600 Ω
750 Ω
C is correct because the charging reactance is inversely proportional to the length of the line, so doubling the length results in half the original reactance.
Length of line l1 = 50 km, Charging reactance Xc1 = 1500 Ω, New length of line l2 = 100 km
Xc=2πfCl1
Identify Relationship
The charging reactance Xc of a transmission line is inversely proportional to its capacitance C, which is directly proportional to its length l. Therefore, Xc is inversely proportional to length l.
Xc∝l1
Set up the Proportionality
Since Xc×l=constant, we can write the relation between two different lengths as Xc1×l1=Xc2×l2.
Xc2=Xc1×l2l1
Calculate New Reactance
Substitute the given values Xc1=1500Ω, l1=50km, and l2=100km into the equation.
Xc2=1500×10050=750Ω
C is correct because the charging reactance is inversely proportional to the length of the line, so doubling the length results in half the original reactance.
This concept is fundamental in power systems; remember that while shunt capacitance increases with line length (lowering reactance), series inductance increases with line length (increasing reactance).