Join 60,000+ competitive exam aspirants
The thickness of insulation layer provided on the conductor in cable depends on
Operating voltage
Current to be carried
Power factor
Both (a) and (b)
Operating voltage
The insulation thickness in an underground cable is primarily determined by the operating voltage it must withstand. As the voltage level increases, the electric stress (g) at the conductor surface increases, requiring a thicker insulation layer to prevent dielectric breakdown.
The insulation thickness in an underground cable is primarily determined by the operating voltage it must withstand. As the voltage level increases, the electric stress (g) at the conductor surface increases, requiring a thicker insulation layer to prevent dielectric breakdown.
gmaxтАЛ=rln(R/r)VтАЛ тАФ maximum dielectric stress at the conductor surface
gminтАЛ=Rln(R/r)VтАЛ тАФ minimum dielectric stress at the sheath
The electric stress at any point at a distance x from the conductor center is given by g=xln(R/r)VтАЛ. To keep the maximum stress below the dielectric strength of the insulating material, the insulation thickness (RтИТr) must be increased proportionally as the operating voltage V increases.
Insulation thickness is inversely proportional to the dielectric strength of the material used.
Higher operating voltages result in higher potential gradients, requiring increased radial thickness.
Current carrying capacity affects the conductor cross-section (area), not the thickness of the insulation layer directly.
Dielectric losses and thermal stability also influence the selection of insulating material.
Prevents arcing between the conductor and the metallic sheath.
Reduces leakage current flow through the insulation.
Excessive thickness increases cable capacitance and charging current.
Thicker insulation increases the total weight and cost of the cable.
Underground transmission lines
Submarine power cables
Distribution network feeders
Current carrying capacity determines the cross-sectional area of the copper or aluminum conductor (based on temperature rise limitations).
Power factor is a system performance parameter and does not directly dictate the physical insulation thickness.
A is correct тАФ The insulation thickness is primarily governed by the operating voltage to ensure the electric stress remains within the permissible dielectric strength of the material.
Always remember: Voltage decides Insulation Thickness (thickness for withstand), while Current decides Conductor Cross-section (area for heat dissipation).