Which of the following is not a DC shunt motor starter?
Two-Point Starter
Three-Point Starter
Four-Point Starter
None of these
Two-Point Starter
A Two-Point starter is exclusively used for DC series motors. DC shunt motors require starters with a No-Volt Coil (NVC) connected either in series with the field winding (3-point starter) or across the supply via a current-limiting resistor (4-point starter) to handle field variation.
A Two-Point starter is exclusively used for DC series motors. DC shunt motors require starters with a No-Volt Coil (NVC) connected either in series with the field winding (3-point starter) or across the supply via a current-limiting resistor (4-point starter) to handle field variation.
IaтАЛ=RaтАЛ+RstarterтАЛVтИТEbтАЛтАЛ тАФ Starting armature current of DC motor
EbтАЛ=60A╬жZNPтАЛ тАФ Back EMF relationship with flux and speed
During startup, a DC motor's back EMF EbтАЛ is zero, causing a very high armature current IaтАЛ=RaтАЛVтАЛ. A starter introduces external resistance in series with the armature to limit initial current. In a 2-point starter, the holding coil is connected in series with the armature, which makes it unsuitable for shunt motors where the armature current varies drastically with load.
A 2-Point starter has only two terminals: Line (L) and Armature (A).
In a 2-point starter, the No-Volt Coil (NVC) is connected in series with the armature winding.
A 3-Point starter is used for DC shunt motors, but NVC is in series with the shunt field, causing issues during field weakening.
A 4-Point starter provides an independent circuit for the NVC, making it ideal for wide speed control of DC shunt motors.
2-point starters are simple and robust for series motor applications.
3-point and 4-point starters protect shunt motors against overloads and loss of supply voltage.
2-point starters cannot protect DC shunt motors because the shunt field is not connected to the NVC circuit.
3-point starters may trip accidentally when speed is controlled above rated speed by field rheostat adjustment.
Two-Point Starter: Electric traction, cranes, and hoists driven by DC series motors.
Three-Point & Four-Point Starters: Lathes, blowers, machine tools, and variable-speed DC shunt drives.
| Feature | Two-Point Starter | Three/Four-Point Starter |
|---|---|---|
Terminals | Two (L, A) | Three (L, A, F) or Four (L, N, A, F) |
NVC Connection | In series with Armature | In series with Field (3-point) or directly across Supply (4-point) |
Motor Compatibility | DC Series Motor only | DC Shunt and Compound Motors |
Option B (Three-Point Starter) is a standard DC shunt motor starter, but its handle may release if the field current is reduced too much during speed control.
Option C (Four-Point Starter) solves the issue of the 3-point starter by connecting the NVC independently across the line with a current-limiting resistor.
A is correct тАФ The Two-Point starter is specifically used for DC series motors, while Three-Point and Four-Point starters are used for DC shunt motors.
Remember: 2-Point = Series motor; 3-Point = Shunt/Compound (normal control); 4-Point = Shunt/Compound (wide speed control via field flux reduction).