The side face reinforcement, if required, in a T-beam will be ______.
0. 1 % of the web area
0. 15 % of the web area
0. 2 % to 0. 3 % of the web area depending upon the breadth of the slab
half the longitudinal reinforcement
0. 1 % of the web area
Side face reinforcement is provided in deep beams or large T-beams to control cracking due to lateral expansion and shrinkage. As per the code, the minimum reinforcement provided on each side face is 0.1% of the web area.
IS 456:2000 Cl. 26.5.1.3
Side face reinforcement is provided in deep beams or large T-beams to control cracking due to lateral expansion and shrinkage. As per the code, the minimum reinforcement provided on each side face is 0.1% of the web area.
Ast,sideтАЛтЙе0.001├ЧBwтАЛ├ЧDwтАЛ тАФ where Ast,sideтАЛ is the reinforcement area on one face, BwтАЛ is web breadth, and DwтАЛ is web depth.
When the depth of the web in a beam exceeds 750┬аmm, there is a risk of thermal and shrinkage cracks on the side faces. Providing distributed steel on the sides limits the width of these cracks by binding the concrete mass together.
Required when depth of web exceeds 750┬аmm.
Reinforcement should be distributed equally on two faces.
Spacing of side face reinforcement should not exceed 300┬аmm or web thickness.
Used to prevent deep beam shear cracking and shrinkage effects.
Improved crack width control
Enhanced structural integrity against shrinkage
Increased steel weight
Minor construction complexity
Deep T-beams
Heavy transfer girders
Large-span reinforced concrete beams
The total side face reinforcement is 0.1% of the web area, implying 0.05% on each face if split, though the clause defines 0.1% as the requirement applied to the web area.
The 750 mm depth criterion is a critical design threshold in IS 456.
A is correct тАФ The code specifies a minimum reinforcement of 0.1% of the web area for side face reinforcement when beam depth exceeds 750┬аmm.
Always link the 750┬аmm depth limit to side face reinforcement requirements; it is a favorite for numerical and theoretical questions in civil engineering exams.